Model NumberPower Out Max (kW)Input Voltage (VAC)Output Voltage Range (VDC)Output Current Max (A)Cooling
OPUS C 24 5.5 R 12U F5.5180 - 27521 - 31229ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)21
V1 Out Nom (V)24
V1 Out Max (V)31
Efficiency Rating (%)90
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+ or VIDI+ I/O
OPUS C 220 8 R 12U F8.0180 - 275189 - 26533ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)189
V1 Out Nom (V)220
V1 Out Max (V)265
Efficiency Rating (%)91
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+ or VIDI+ I/O
OPUS C 48 8 R 12U P8.0180 - 27542 - 58164ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)42
V1 Out Nom (V)48
V1 Out Max (V)58
Efficiency Rating (%)91
Operating Altitude (m)200
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+ or VIDI+ I/O
OPUS C 48 8 R 12U F8.0180 - 27542 - 58164ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)42
V1 Out Nom (V)48
V1 Out Max (V)58
Efficiency Rating (%)91
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+ or VIDI+ I/O
OPUS C 60 8 R 12U F8.0180 - 27551 - 72134ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)51
V1 Out Nom (V)60
V1 Out Max (V)72
Efficiency Rating (%)91
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+ or VIDI+ I/O
OPUS C 12U are compact, 19" rack-mount DC power systems that offer a robust, free convection cooled, N+1 redundant backup power solution for telecommunications, process industry, transmission and distribution substations and other critical infrastructure applications.

The OPUS C 12U is a 19" self-contained rack-mount power system consisting of the MRC series rectifiers, VIDI+ controllers, mains and battery connections, and a wide selection of load distribution options. OPUS C systems are available in 24, 48, 60, 110, 125 and 220 VDC standard outputs and have a max output power of 8.0 kW.

The systems meet IEC 60950-1 safety standards and the following EMC standards: Emissions: IEC/EN 61000-6-4, Immunity: IEC/EN 61000-6-2, Harmonics: IEC/EN 61000-3-2, and Voltage Fluctuations & Flicker: IEC/EN 61000-3-3.

System options include a battery LVD, load LVD, extra battery connections, temperature sensor, wall-mount kit and IP21 kit.

All Efore DC power systems are configurable and scalable to meet individual application requirements. Contact us to show you how we can develop a custom system for you.

Ask our expert about OPUS C 12U DC Power Systems

CAPTCHA
This question is for testing whether or not you are a human visitor and to prevent automated spam submissions.