Model NumberPower Out Max (kW)Input Voltage (VAC)Output Voltage Range (VDC)Output Current Max (A)Cooling
OPUS C 24 3.3 R 7U F3.3180 - 27521 - 31229ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions3
V1 Out Min (V)21
V1 Out Nom (V)24
V1 Out Max (V)31
Efficiency Rating (%)90
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
OPUS C 48 4.8 R 7U F4.8180 - 27542 - 58164ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions3
V1 Out Min (V)42
V1 Out Nom (V)48
V1 Out Max (V)58
Efficiency Rating (%)92
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+
OPUS C 60 4.8 R 7U F4.8180 - 27551 - 72134ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions3
V1 Out Min (V)51
V1 Out Nom (V)60
V1 Out Max (V)72
Efficiency Rating (%)91
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+
OPUS C 110 4.8 R 7U F4.8180 - 27597 - 13272ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions3
V1 Out Min (V)97
V1 Out Nom (V)110
V1 Out Max (V)132
Convection Rating (W)92
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+
OPUS C 220 4.8 R 7U F4.8180 - 275189 - 26536ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions3
V1 Out Min (V)189
V1 Out Nom (V)220
V1 Out Max (V)265
Efficiency Rating (%)91
Operating Altitude (m)2000
Operating temperature range-5 to 45°C
SafetyIEC/EN 60950-1
IP RatingIP20
Control & MonitoringVIDI+
OPUS C 7U 19" rack power systems are robust, N+1 redundant, free convection cooled backup power solutions for critical infrastructure applications such as distribution and transmission substations, process control industries and telecommunications.

The OPUS C 7U 19" rack-mount power system are configured to customer specifications utilizing OPUS C standard building blocks consisting of the MRC series rectifiers, VIDI+ controllers, mains and battery connections, and a wide selection of load distribution options. OPUS C systems are available in  24, 48, 60, 110, 125 and 220 VDC standard output variants and have a max output power of 4.8 kW (3.3 kW for 24 VDC models).

System options include a battery LVD, temperature sensor, wall-mount kit and IP21 cover kit.

The systems meet IEC 60950-1 safety standards and the following EMC standards: Emissions: IEC/EN 61000-6-4, Immunity: IEC/EN 61000-6-2, Harmonics: IEC/EN 61000-3-2, and Voltage Fluctuations & Flicker: IEC/EN 61000-3-3.

All Efore DC power systems are configurable and scalable to meet individual application requirements. Contact us to show you how we can develop a custom system for you.

Ask our expert about OPUS C 7U DC Power Systems