Model NumberPower Out Max (kW)Input Voltage (VAC)Output Voltage Range (VDC)Output Current Max (A)Cooling
OPUS HE 48-10.0 R12U P10.085 - 30042 - 59208.5Natural ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)42
V1 Out Nom (V)48
V1 Out Max (V)59
Efficiency Rating (%)97
Operating Altitude (m)2000
Operating temperature range-25 to +60 Deg C
SafetyEN/IEC 62368-1, EN 50124-1 Railway
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 110-10.0 R12U F10.085 - 30090 - 15092.5Natural ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)90
V1 Out Nom (V)110
V1 Out Max (V)150
Efficiency Rating (%)97
Operating Altitude (m)2000
Operating temperature range-25 to +60 Deg C
SafetyEN/IEC 62368-1, EN 50124-1 Railway
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 24-7.5 R12U F7.585 - 30021 - 33312.5Natural ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)21
V1 Out Nom (V)24
V1 Out Max (V)33
Efficiency Rating (%)97
Operating Altitude (m)2000
Operating temperature range-25 to +60 Deg C
SafetyEN61439-1, EN61439-2; Railway EN51024-1
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 220-10.0 R12U F10.085 - 300178 - 28046.3Natural ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)178
V1 Out Nom (V)220
V1 Out Max (V)280
Efficiency Rating (%)97
Operating Altitude (m)2000
Operating temperature range-25 to +60 Deg C
SafetyEN61439-1, EN61439-2; Railway EN51024-1
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 60-10.0 R12U P1085 - 30051 - 72166.7Natural ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)51
V1 Out Nom (V)60
V1 Out Max (V)72
Efficiency Rating (%)97
Operating Altitude (m)2000
Operating temperature range-25 to +60 Deg C
SafetyEN61439-1, EN61439-2; Railway EN51024-1
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 125-10.0 R12U F1085 - 300100 - 16083.3Natural ConvectionMore info
Product Specifications
Max # Outputs1
Module Positions5
V1 Out Min (V)100
V1 Out Nom (V)125
V1 Out Max (V)160
Efficiency Rating (%)97
Operating Altitude (m)2000
Operating temperature range-25 to +60 Deg C
SafetyEN61439-1, EN61439-2; Railway EN51024-1
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE power systems offer a robust, free air convection cooled, N+1 redundant backup power solution for critical infrastructure applications such as transmission and distribution substations, process industries, railway signaling and substations, and telecommunications.

The OPUS HE system consists of MHE rectifiers, VIDI+ controllers, connections for mains and battery, and load distribution MCB. Offered in a 19" 12U rack, the system delivers a maximum 10 kW output power at 48, 60, 110, 125 and 200 VDC, and 6.0 kW at 24 VDC outputs.

The 19" 12U rack system provides slots for a maximum of five (5) MHE rectifier modules. Load distribution configuration of MCB quantity and current ratings can be configured at time of order. Wall mounting, IP21 cover kit, temperature sensor and BLVD are available as options.

All Efore DC power systems are configurable and scalable to meet individual application requirements. Contact us to learn how we can create a custom system for you.

Ask our expert about OPUS HE 12U Rack-Mount Power Systems

When you submit this form, our specialist will be in touch with you by email or telephone. By submitting the form you accept our Privacy Policy.

CAPTCHA