Model NumberPower Out Max (kW)Input Voltage (VAC)Output Voltage Range (VDC)Output Current Max (A)Cooling
OPUS HE 60-6.0 R7U F6.0100 - 25051 - 72100Natural ConvectionMore info
Product Specifications
Module Positions3
V1 Out Min (V)51
V1 Out Nom (V)60
V1 Out Max (V)72
Output Current Min (A)33.3
Efficiency Rating (%)97
Operating Altitude (m)3000
Operating temperature range-25 to +60 Deg C
SafetyRack: EN61439-1, EN61439-2
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 125-6.0 R7U F6.0100 - 250100 - 16050Natural ConvectionMore info
Product Specifications
Module Positions3
V1 Out Min (V)100
V1 Out Nom (V)125
V1 Out Max (V)160
Output Current Min (A)16.7
Efficiency Rating (%)97
Operating Altitude (m)3000
Operating temperature range-25 to +60 Deg C
SafetyRack: EN61439-1, EN61439-2
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 125-6.0 R7U F6.0100 - 250178 - 28027.8Natural ConvectionMore info
Product Specifications
Module Positions3
V1 Out Min (V)178
V1 Out Nom (V)220
V1 Out Max (V)280
Output Current Min (A)9.3
Efficiency Rating (%)97
Operating Altitude (m)3000
Operating temperature range-25 to +60 Deg C
SafetyRack: EN61439-1, EN61439-2
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 110-6.0 R7U F6.0100 - 25090 - 15055.5Natural ConvectionMore info
Product Specifications
Module Positions3
V1 Out Min (V)90
V1 Out Nom (V)110
V1 Out Max (V)150
Output Current Min (A)18.5
Efficiency Rating (%)97
Operating Altitude (m)3000
Operating temperature range-25 to +60 Deg C
SafetyRack: EN61439-1, EN61439-2
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 24-4.5 R7U F4.5100 - 25021 - 33187.5Natural ConvectionMore info
Product Specifications
Module Positions3
V1 Out Min (V)21
V1 Out Nom (V)24
V1 Out Max (V)33
Output Current Min (A)62.5
Efficiency Rating (%)97
Operating Altitude (m)3000
Operating temperature range-25 to +60 Deg C
SafetyRack: EN61439-1, EN61439-2
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE 48-6.0 R7U F6.0100 - 25042 - 59125Natural ConvectionMore info
Product Specifications
Module Positions3
V1 Out Min (V)42
V1 Out Nom (V)48
V1 Out Max (V)59
Output Current Min (A)41.7
Efficiency Rating (%)97
Operating Altitude (m)3000
Operating temperature range-25 to +60 Deg C
SafetyRack: EN61439-1, EN61439-2
IP RatingIP20
Control & MonitoringVIDI+ Controller
OPUS HE R7U SLAVE 5 x MHEMore info
Product Specifications
Module Positions5
The new OPUS HE 7U is a high efficiency rack-mount DC power system that is designed for critical infrastructure applications such as telecommunications, process industries, railway signaling and substations, and transmission and distribution substations.

This new high efficiency rack-mount power system supports up to three (3) MHE series high efficiency rectifiers, but may be expanded by using a master-slave configuration, increasing the power capability to 16kW. Available as a 19" 7U rack-mountable package, the base system delivers a maximum 6 kW output power at 48, 60, 110, 125 and 220 VDC, and 4.5 kW at 24 VDC outputs.

Additional features include Efore's VIDI+ controllers, connections for mains and 1 full current battery string, and a bulk screw terminal for external load distribution . Optional accessories include wall-mount and IP21 cover kits, temperature sensor and Battery LVD.

All Efore DC power systems are configurable and scalable to meet individual application requirements. Contact us to learn how we can create a custom system for you. 

 

Ask our expert about OPUS HE 7U Rack-mount Power Systems